Trip amplifier KFD2-CRG2-EX1.D Pepperl+Fuchs 255620
Trip amplifier KFD2-CRG2-EX1.D Pepperl+Fuchs 255620

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

KFD2-CRG2-EX1.D 255620 Pepperl+Fuchs Trip amplifier

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

KFD2-CRG2-EX1.D

Part number

255620

Type

Trip amplifier

Description

Transmitter Power Supply KFD2-CRG2-Ex1.D

Stock availability:

On request

576.26 €

Need cheaper?

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications KFD2-CRG2-EX1.D 255620

This isolated barrier is used for intrinsic safety applications. The device supplies 2-wire and 3-wire transmitters, and can also be used with current sources. Two relays and an active 0/4 mA ... 20 mA current source are available as outputs. The relay contacts and the current output can be integrated in security-relevant circuits. The current output is easily scaled. On the display the measured value can be indicated in various physical units. The device is easily configured by the use of keypad or with the PACTware configuration software. The input has a line fault detection. A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output. For additional information, refer to the manual and www.pepperl-fuchs.com.

Features KFD2-CRG2-EX1.D 255620

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionPower Rail or terminals 23+, 24-
Rated voltage20 ... 30 V DC
Rated currentapprox. 130 mA
Power dissipation2 W
Power consumption2.5 W
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
Connectionterminals 1, 2, 3
Input I
Input signal0/4 ... 20 mA
Available voltage&ge, 15 V at 20 mA
Open circuit voltage/short-circuit current24 V / 33 mA
Input resistance45 &Omega, (terminals 2, 3)
Line fault detectionbreakage I 22 mA
Output
Connection sidecontrol side
Connectionoutput I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7-
Output signal0 ... 20 mA or 4 ... 20 mA
Output I, IIsignal, relay
Contact loading250 V AC / 2 A / cos &phi, &ge, 0.7 , 40 DC / 2 A
Mechanical life5 x 107 switching cycles
Output IIISignal, analog
Current range0 ... 20 mA or 4 ... 20 mA
Open loop voltagemax. 24 V DC
Loadmax. 650 &Omega,
Fault signaldownscale I &le, 3.6 mA, upscale I &ge, 21 mA (acc. NAMUR NE43)
Energized/De-energized delay0 ... 250 s , adjustable
Transfer characteristics
Input I
Accuracy< 30 µ,A
Influence of ambient temperature0.003 %/K (30 ppm)
Output I, II
Response delay&le, 200 ms at bounce from 0 ... 20 mA
Output III
Resolution&le, 10 µ,A
Accuracy< 20 µ,A
Influence of ambient temperature0.005 %/K (50 ppm)
Reaction time< 650 ms at bounce from 0 ... 20 mA at the input, 90 % of output full-scale value
Galvanic isolation
Input/Other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, IIIreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/power supply and collective errorfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Interface/power supply and collective errorfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Indicators/settings
Display elementsLEDs , display
Control elementsControl panel
Configurationvia operating buttons via PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Mass300 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateTÜV 01 ATEX 1701
Marking II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
InputEx ia
Supply
Maximum safe voltage40 V DC (Attention! The rated voltage can be lower.)
Equipmentterminals 1+, 3-
Voltage Uo25.8 V
Current Io93 mA
Power Po0.603 W
Equipmentterminals 2-, 3
Voltage Ui< 30 V
Current Ii115 mA
Voltage Uo5 V
Current Io0.3 mA
Power Po0.3 mW
Equipmentterminals 1+, 2 / 3-
Voltage Uo25.8 V
Current Io112 mA
Power Po720 mW
Output I, IIterminals 10, 11, 12, 16, 17, 18 non-intrinsically safe
Maximum safe voltage253 V AC / 40 V DC (Attention! Um is no rated voltage.)
Contact loading253 V AC/2 A/cos &phi, > 0.7, 40 V DC/2 A resistive load (TÜV 01 ATEX 1701)
Output IIIterminals 8+, 7- non-intrinsically safe
Maximum safe voltage Um40 V (Attention! The rated voltage can be lower.)
InterfaceRS 232
Maximum safe voltage40 V (Attention! The rated voltage can be lower.) , RS 232
CertificateTÜV 02 ATEX 1885 X
Marking II 3G Ex nA nC IIC T4
Output I, II
Contact loading50 V AC/2 A/cos &phi, > 0.7, 40 V DC/1 A resistive load
Galvanic isolation
Input/Other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing16-554FM-12 (cFMus)
UL approvalE223772
IECEx approvalIECEx TUN 09.0007
Approved for[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) - FDT framework PACTware 4.1 - device type manager DTM Interface Technology - adapter K-ADP-USB